首页 | 本学科首页   官方微博 | 高级检索  
   检索      

湿式报警阀组漏误报原因及对策
引用本文:许剑方.湿式报警阀组漏误报原因及对策[J].中国人民武装警察部队学院学报,2009,25(12):55-57.
作者姓名:许剑方
作者单位:福州市消防支队,福建福州350005
摘    要:从自动喷水灭火系统工程验收和日常防火监督检查发现的问题出发,就湿式报警阀组漏、误报原因进行深入分析,指出了设计不合理、水力警铃安装位置不当、未设延迟器、管网中气囊未排除和施工安装不到位等造成湿式报警阀组漏、误报的常见原因,并提出把好设计、审核、施工、安装等环节,消除湿式报警阀组漏、误报的隐患。

关 键 词:湿式报警阀组  漏报  误报  原因  对策

On the Causes of False Alarming by Wet System Alarm Valves
Institution:XU Jian - fang ( Fuzhou Municipal Fire Brigade, Fujian Province 350005, China)
Abstract:This paper analyzes the causes of false alarming by wet alarming,pointing out the improper design with this system,the wrong place to position the water motor alarm,the lack of retardant chambers,the air block in the pipes of this system and the unqualifying construction of this system based on the verification of automatic water spray fire fighting system and the problems with the daily management.Some suggestions about improving these problems are made in this paper.
Keywords:wet system alarm valves  failure to report  false alarm  cause  measures
本文献已被 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号